DRC-40 series

40W Single Output with Battery Charger (UPS Function)

DRC-40 is a 40W AC/DC DIN rail type security power supply series. In addition to the primary output, there is a charger output with a smaller rated current, enabling the backup power supply application the security access systems require. DRC-40 accepts the universal input between 90VAC and 264VAC, and supplies 13.8 VDC and 27.6VDC at output, respectively.

Choose your option:

Description

DRC-40 series

40W Single Output with Battery Charger (UPS Function)

DRC-40 is a 40W AC/DC DIN rail type security power supply series. In addition to the primary output, there is a charger output with a smaller rated current, enabling the backup power supply application the security access systems require. DRC-40 accepts the universal input between 90VAC and 264VAC, and supplies 13.8 VDC and 27.6VDC at output, respectively. With the efficiency up to 87%, it can operate with air convection cooling under -30℃ through 70℃. In addition to the key protection features such as overload protection, over voltage protection, battery low cut off, and battery reverse polarity protection (by fuse), the alarm signal for AC OK and battery low signaling is provided, via TTL open collector output for the standard model ( via relay contact output as the optional model), to facilitate the system design.

Features (DRC-40) :

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage
  • Battery low protection / Battery reverse polarity protection by fuse
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Alarm signal for AC OK and Battery low (via TTL open collector, optional via relay)
  • Cooling by free air convection
  • Pass LPS
  • LED indicator for power on
  • 100% full load burn-in test

Applications :

  • Security system
  • Emergency lighting system
  • Alarm system
  • DC UPS system
  • Central monitoring system
  • Access systems

Additional information

Weight 13.6 kg
Dimensions 4.0 × 9.0 × 10.0 cm
DRC-40 Types :

DRC-40A, DRC-40B

Specifications

Model DRC-40A DRC-40B
Output OUTPUT NUMBER CH1 CH2 CH1 CH2
DC VOLTAGE 13.8V 13.8V 27.6V 27.6V
RATED CURRENT 1.9A 1A 0.95A 0.5A
CURRENT RANGE 0 ~ 2.9A ——– 0 ~ 1.45A ——–
RATED POWER 40.02W 40.02W
RIPPLE & NOISE (max.) 120mVp-p ——– 200mVp-p ——–
VOLTAGE ADJ. RANGE CH1: 12 ~ 15V CH1: 24 ~ 30V
VOLTAGE TOLERANCE ±1.0% ——– ±1.0% ——–
LINE REGULATION ±0.5% ——– ±0.5% ——–
LOAD REGULATION ±0.5% ——– ±0.5% ——–
SETUP, RISE TIME 400ms, 50ms/230VAC 800ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC 10ms/115VAC at full load
Input VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE 47~63Hz
EFFICIENCY (Typ.) 86% 87%
AC CURRENT (Typ.) 0.8A/115VAC 0.6A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC 60A/230VAC